R609 *Connect main power safely. The following devices shall be connected with 6 AWG (7 SWG or 16 mm2) copper wire or larger as shown in Figure 8‑9:
A.
1
B. a single pair of Anderson Power Products (or APP) 2-pole SB type connectors,
C. the 1 main 120-Amp (120A) surface mount circuit breaker (Cooper Bussman P/N CB185-120, CB185F-120, CB285-120 CB285F-120, CB285120F or Optifuse P/N 153120, 253120), and
D.
the 1 power distribution device (CTR Electronics Power
Distribution Panel,
No additional devices or modifications shall be permitted with the following exceptions:
E. Monitoring circuitry permitted by R625
F. SB-50 to SB-120 adapters, provided they have been presented for Inspection.
Figure 8‑7 Electrical connection diagram
“SB type” refers to SB type only (e.g. SB-50, SB-120, etc.), not SBS or any other part type beginning with SB. All batteries supplied by FIRST (such as Spare Parts and international batteries) will have a red or pink SB50 connector installed which may not be removed.
The pink connectors included in the