R615       *Power roboRIO as specified. The roboRIO power input must be connected to either:

A.     the dedicated supply terminals on the PDP shown in Figure 9‑11 or

Figure 9‑11 roboRIO power source on a PDP

B.     the terminals of 1 of the non-switchable fused channels on the PDH (20,21,22) with a 10A fuse installed in the associated fuse holder.

No other electrical load shall be connected to that channel.

Figure 9‑12 roboRIO power source on a PDH

Similar Rules

Rule R617
R617       *Power radio as specified – Part 2. The device supplying power to the wireless bridge per R616 must be connected to either:
Rule R616
R616       *Power radio as specified – Part 1. The wireless bridge (radio) power must be supplied by either:
Rule R610
R610       *1 breaker per circuit. All circuits, with the exceptions of those listed in R615 and R617, must connect to, and have power sourced solely by, a single protected 12VDC WAGO connector pair (i.e. the load terminals, as shown in Figure 9‑10) of the PDP/PDH, not the M6 cap screws.
Rule R618
R618       *Use PDP/PDH terminals as designed. Only 1 wire shall be connected to each terminal on the PDP/PDH.