R621 *Protect circuits with appropriate circuit breakers. Each branch circuit must be protected by 1 and only 1 circuit breaker or fuse on the PD per Table 8‑3. No other electrical load can be connected to the breaker or fuse supplying this circuit with the exception of devices downstream of a permitted motor power adapter board placed between the PD and a motor controller (WCP-1380, WCP-1903, WCP-1904, RF-4003, RF-4004, RF-4005).
Table 8‑3 Branch circuit protection requirements
|
Branch Circuit |
Circuit Breaker/ Fuse Value |
Quantity Allowed Per Breaker |
|
Motor Controller |
Up to 40A |
1 |
|
|
Up to 40A |
No limit |
|
Automation Direct Relay 40A (*6M40*) |
Up to 40A |
1 |
|
Fans permitted per R501 and not
already part of |
Up to 20A |
No limit |
|
Spike Relay Module |
Up to 20A |
1 |
|
Automation Direct Relay 25A (*6M25*) |
Up to 20A |
1 |
|
|
Up to 20A |
1 |
|
Servo Power Module/Servo Hub |
Up to 20A |
1 |
|
Additional |
Up to 20A |
3 total |
|
Automation Direct Relay 12A (*6M12*) |
Up to 10A |
1 |
This rule does not prohibit the use of smaller value
breakers in the PD or any fuses or breakers within
Fans permitted per R501 may also be included
within